The CoDeSys Driver was designed specifically to get in communication with 3S Software softPLC, connected through TCP/IP network protocols.
An instance of the CoDeSys SoftPLC can be installed on a desktop computer or on a Windows CE panel; the driver is able to access both.
Our driver support two different PLC version: 2.3 and 3. The runtime and the Programming environment are different for the two versions, for the configuration of the 3S system, please refer to their documentation.
The version 3 PLC need a 3S dll, in order to complete the connection. The GwClient.dll must be present in the client system, in the Supervisor directory or in a directory included in the path environment variable.
In order to establish the connection with the PLC, a valid program must run and the program symbols must be exported. Please, refer to the PLC and development environment documentation for more information and operating procedures.
Release
11.4.1.5 dbl267
Interface Device
CoDeSys Runtime Ver. 2.3, Ver. 3.x
Manufacturer
3S CoDeSys
Requirement/Description
Require Ethernet board, GwClient.dll in the client and Supervisor system, 3S dll for connecting to version 3 PLC.
3S CoDeSys TCP/IP Protocol supported by the PLCHandler library
License Code
Require License Code
Import Tags
Support Import Tags
Operating System
WIN 32/64
WIN CE
Downloads
|
|
|
For more information on this driver please refer to the help relating to the driver in Movicon 11