Problems solved with release: 11.0.0.1015
Build: 11.0.0.1015
Release Date: 30th January 2009

Minor Problems

ID

TOPIC

PROBLEM SOLVED

4522

Tools

When the "Tag-Alarm Generator" Tool could not read the file it was set with, it would overwrite it with leaving it empty: length = zero bytes.

 

4552

Design

A Project's startup screen would not load maximized on video screen even though the project had been enabled with the "Pre-Load Screens" and "Start Full Screen". This problem started happening with the build 1014.

 

4505

Report Management

The output of a Textual Report command would generate an file in error in cases when the layout connected one of the "{ } \" chars. as text.

 

4475

Report Management

The Text Report print always failed to work correctly when more than one page had to be printed. Just the "Print" command failed to work and only in cases where the report layout was in Rich Text Format (RTF). All the other commands in the same category continued working correctly.

 

4477

WinCE OS

The quality of Textual Report  in Rich Text format (RTF) print was not very good when using Windows CE.  Not all the line endings would fit on the page and therefore left out.

 

4473

Tools

The "Tag Alarm Generator" could not be used with unicode, encrypted and/or zipped projects.

 

4496

Schedulers Resource

The Scheduler object's hour plan set in development mode would not load in runtime correctly as all the pre-scheduled hours were moved one day ahead, therefore the Monday hour plan would be used on Tuesday, etc. This problem started occurring with the 11.0 version.

 

4520

Tools

The "Tag Alarm Generator" tool would not display and deal with variables that had unicode chars. when in the RealTimeDB.

 

3362

Screen Objects

Updating a 10.2 version project that contained a "Scheduler Window" object, it would show the "Day7" text instead of showing "Sunday".

 

4513

Design

The wizard for creating "Template Projects" and "Empty Projects" would create alarm "Messages" as alarm thresholds instead.

 

4486

DOM (Document Object Model)

The "ConnectServer" function from the "OPCClientObjCmdTarget" interface now carries out a forced OPC Server disconnection, if unable to retrieve the OPC Server's status. This will allow this function to be used for reconnecting to an OPC Server that crashed, even though the DCOM did not notify the Movicon Client that the Server was no longer active.

 

4491

Screen Objects

Items within the "Scheduler Window" object's combo box, used for selecting schedulers or variables, would not always get selected. This generally happened when the drop down list opened for the first time. Once closed and re-opened it became possible to select items listed.