Problems solved with release: 11.2.1084
Build: 11.2.1084
Release Date: 8th February 2011

ID

TOPIC

PROBLEM SOLVED

7418

Design

Movicon, in certain situations, would raise an error when editing alarm lists if Alarm's had been enabled with the notification facility.  

 

7467

Report Management

Problems occurred when using Reports created with the 11.1 version due to changing the  DevXpress versions (from v.8.2 to v. 9.3).

 

7339

Setup

The Movicon 11.2 DVD Logicon setup would not install if Movicon 11.2 had not been installed first.

 

7543

WebClient

The fast Change page in the Web Client would raise and error in the Server.

 

 

Minor Problems

ID

TOPIC

PROBLEM SOLVED

7483

Alarm Management

Some alarm transactions would go missing if the variable associated to the alarm change too quickly.

 

6273

Basic Scripts

An error would show in the MouseMove() definition when using the .NET directive in the Movicon script.  This problem has been fixed with the WinWrap 9.3 version that for the time being is provided by Progea on request if needed.

 

7384

Basic Scripts

Recording the Historical Log IMDB would cause the Drivers tables to recreate for each new entry, zeroing the already existing contents.

 

7397

Basic Scripts

Sub definitions would not get acknowledged when setting script for .Net syntax with the WinWrap Basic 9.30.61 version.

 

7249

Basic Scripts

Too much memory space was used when using XML object in Movicon .NET script.  This problem has been fixed with the WinWrap 9.3 version that for the time being is provided by Progea on request if needed.

 

7439

Comm.Drivers

When starting a project up, a DataLogger set for record on change would record twice.

 

7659

Comm.Drivers

When exchanging an array type that wasn't in byte with the Communication Driver it would not work properly.  Only the first 10 bytes would get exchanged.

 

7534

Comm.Drivers

If the "Prompt Control Window' option was disabled in the Historical Log, TraceDB display windows etc, their columns could not be resized.

 

7398

Data Loggers Management

When inserting a basic script expression in a DataLogger, the field would get created in text type if the table had been created in development mode.

 

7330

Design

In certain conditions, the mouse click with the CTRL pressed down on an "Embedded Screen" would raise an error in the Movicon application.  

 

7421

Design

DataLogger data could  not be recovered from a midlet application.

 

7335

Design

When using a recipe and evoking the "Create Recipe Screen" command a message would show notifying that screen resource had been edited outside and would user like to reload it.

 

7379

Design

In certain conditions Movicon would raise an error while working without snapping to grid.

 

7391

Design

When inserting resources, such as Screens, Basic Script, etc., which contained a dot in their names, the xml. file would not get created when saving the project.

 

7420

Design

A Child project's  _SysVar_:LastAlarmText system variable did not have any values in either  the Parent or Child projects.

 

7378

Design

The "Area" field for Alarm commands was active for all types of commands instead being active just for "Ack All" and "Reset All".

 

7299

Design

A variable's "Enable Data Statistics" property gave wrong advice.

 

7651

Design

Problems occurred with public symbols in certain situations after selecting the Public Source Container within a screen.

 

7600

Design

Movicon would raise an error after reloading the String Table which had been edited with an external editor beforehand (such as the StringImpExp.exe tool).

 

7329

Design

When selecting a control which activated the text format bar, each time the mouse moved the toolbar would get redesigned, or at least the two combo-boxes within would flicker.

7323

Design

The size of Trend pens in statistical value settings would not work correctly.

 

7664

Design

In certain cases, using a project in SourceSafe mode, when Checking-in one resource, all the resources got requested for checking in.

 

7324

Design

The  "Template Project" wizard plug-in created some objects, such as the Trend and Alarm Windows, with the wrong settings.

 

7552

Historical Log Management

Log files created after ODBC errors would sometimes not get formatted correctly.  For example, message text would get divided on two lines.

 

7358

IL Logic

IL logic could not be used for variable starting with the letter 'K'.

 

7679

Networking

A Client project's TraceDB window could not recover historical data from the Server if the variable's table name had been customized.

 

7442

Networking

A Client project created with Parent/Child architecture with set redundancy options on the Child project, Movicon would freeze when project was being aborted.

 

7673

Networking

The GetVariableDescription function would always return an empty string if executed in a Client project created with Parent-Child architecture.

 

7357

OPC Communication

The error message that Movicon  generated when an OPC item could not be found in the OPC server's address space, did not report the name of the item.

 

7356

OPC Communication

It was not possible to put a structure variable composed with a certain number of  "Bit" elements in communication with a OPC Server Tag in Bool Array type with the same number of elements that the structure variable had.

 

7616

Real Time DB

Launching a project from development mode, variables set in the shared area (input, output or flag), would get considered as belonging to the NOT shared area.

 

7676

Report Management

If a Report created with Report Designer connected to a DataLogger that contained a space in its Datalogger name, the "dataset" would not get created correctly therefore data would not get loaded.

 

7340

Screen Management

A Screen that had been set with more that '1' instance would not open more than once. this would happen if the screen had been closed clicking the "X" on the title bar and not the close button on screen.

 

7080

Screen Management

On screen object animations were not sychronized with the basic script manager.

 

7630

Screen Management

After selecting the "Close and Return Back" it became no longer possible to select a screen name in the "Screen" field.

 

7387

Screen Management

When setting a screen alias, an object contained within an embedded screen would not read the alias value.

 

7405

Screen Management

When inserting the "Capture and Print" command and specifying the name of the screen to be printed, renaming this screen with a new name, this new name would not be applied by the command.

 

7388

Screen Objects

The Trend, upon opening the screen, would not load runtime data when the "Read Data in Background" option had been set.

 

7337

Screen Objects

Local container screen variables of an 'Embedded Screen' would not get read by the Embbed Screen.

 

7265

Screen Objects

In the Data Analysis even though a pen was displayed respecting the 'TimeStamp' column, selecting data, by applying a filter for instance, it would always get selected respecting the "LocalCol" column.

 

7264

Screen Objects

In the Data Analysis the Pen points would get drawn differently when quality = NOT good, according whether the "TimeStamp" or "TimeCol" column was being used.

 

7263

Screen Objects

If a pen's "Use TimeStamp" option had been enabled in the Data Analysis, its points would be put into order according to the TimeStamp column, but the lines were drawn compliant to the TimeCol.

 

7274

Screen Objects

Executing the "Set Screen Alias" command would raise and error in Movicon if not the last command on the list.

 

7292

Screen Objects

The Data Analysis's Progress Bar would have problems while refreshing from Client and every so often would indicate that values were wrong.

 

7287

Screen Objects

In the Data Analysis, displaying data  within the same second, the time axis would not align to the times reported in the point labels.

 

7286

Screen Objects

Milliseconds would not display in the Data Analysis in correspondence to the time axis notches even though enabled to do so.

 

7332

Screen Objects

The "GetLastValidValuePosition" method from the "TrendCmdTarget" would not work correctly.

 

7333

Screen Objects

When a screen was kept in memory (Keep in Memory enabled) it was impossible to force shut down the operating system.

 

7377

Screen Objects

A Tab Group object would not display the screen's name in the tab properly.

 

7471

Screen Objects

Even though the "Show Control Window" option had been disabled, the "List" of a Combo-Box, would always show at the forefront even though its tab order was lower than another object's.

 

7267

Screen Objects

In certain conditions only some of the legend pens would get displayed in the Data Analysis object, leaving out the selected pen's point labels.

 

7183

Screen Objects

Display window column font alignments would not get managed correctly for  window columns.

 

7256

Screen Objects

In the Recipe Manager Window, the recipe selection combo-box list would always stay with default sizes even though the "Text Font" property had been changed.

 

7360

Screen Objects

The text displayed in the "display" part of a Combo-Box would not update when the list of items had changed.

 

7618

Screen Objects

A problem occurred with a screen inserted with diverse "Embedded Screens" overlapping each other, when clicking on the border of an embedded Screen at the forefront, the others behind also responded to the click.  

 

7502

Screen Objects

In certain conditions an object's "Enable Zoom" visibility property would not work correctly.  For example, this object would not disappear if its size became smaller than the percentage set.

 

7381

Screen Objects

The Trend's curves would not get drawn correctly when the "Read Data in Background" option had been enabled.

 

7316

Screen Objects

It became difficult scrolling data in the Data Analysis when selecting the "Month" date range.

 

5443

Screen Objects

A problem arose in the Recipe Manager Window when using the keyboard to edit a cell.  The first character entered would get overwritten by the second character entered.

 

7464

Screen Objects

A Data Analysis would invalidate regions outside its area when it had pens with rectangular styles.

 

7512

Screen Objects

The  "Enable Size" visibility property did not have effect in composed symbols.

 

7451

Screen Objects

There were problems in WinCE in displaying texts used with the "Overlap Image/Text" enabled.

 

7438

Screen Objects

In the Data Analysis, if the "Load Data in Separate Thread" option had been enabled, problems would occur when setting the time scale to "Adjust to values" or "Absolute Ranges.

 

7444

Screen Objects

In particular conditions, if the Trend had an automatic scale, data would not get displayed when the Trend switched from Stop mode to Run mode.

 

7478

Setup

The list of DevExpress assemblies installed with Movicon 11.2 were not all correct.

 

7450

Setup

The "DevExpress.XtraRichEdit.v9.3" component would not get registered while installing Movicon, later causing problems in Web report.

 

7514

Setup

The "Time.msxz" library would get installed also after it had been renamed in  "Clocks.msxz".

 

7413

Tools

Even though the "Acknowledge Scada Alarm" option from the Alarm Dispatcher's VOICE plug-in had been enabled, the alarm's Reset would not work if in the OFF(ACK) state.

 

7400

Tools

When using the alphanumeric pad to insert the password in the  EditUsr.exe tool, the actual password would be revealed  instead of being concealed.  

 

7372

Tools

Problems would occur while importing an  ".csv" file in to the Movicon String Table if strings contained the "<" or ">" chars, being chars interpreted as opening/closing of xml tags.

 

7480

User Interface

The window for entering the software license became unusable in panels with 640x480 or smaller resolutions.  This has been fixed so when pressing the "CTRL"  key on the command to open the License Requirement window you will find a button for opening the soft key window in reduced size  through which to enter the software code.  

 

7448

User Interface

In certain conditions Movicon would raise an error during the stop mode of projects launched with the  MoviconRunTime.exe.

 

7433

User Interface

In certain cases evoking the "Wait Time" system command while closing the project would raise an error in Movicon.

 

7399

Users Management

The first Logon operation performed after project startup, would not execute the logon script linked to the user.

 

6925

Users Management

A Runtime User profile would not load when logging into the Windows domain.  Only Users created in development mode could gain access to the Windows Domain.

 

7369

Users Management

The window for user password re-entries would also accept blank password entries. This would happen if the "Min. Password Length" property had been set to zero. Now this property requires at least one character when set at zero.

 

7479

WebClient

Using a Web client connected to a Server project running on WinCE, would use up a lot of memory navigating screens if they had been set with a value minor to 100 in their "We Client Quality" properties.

 

6938

WebClient

The WebClient midlet in BlackBerry phones was not working properly.

 

6803

WinCE OS

Movicon could not continue with new recording when having problems with ".sdf",  database files in WindowsCE.  Now when this happens, the files are cancelled and then created again.  

 

7454

WinCE OS

In certain situations the Numeric Pad would not show the minimum and maximum limits correctly.