ID
|
TOPIC
|
PROBLEM SOLVED
|
8665
|
Comm.Drivers
|
Executing a project save while modifying it online, would reload all the communication tasks in use at that moment. This would then cause a slow down in communications. Now only the tasks where variable dynamic link settings have been changed will be reloaded.
|
6880
|
Comm.Drivers
|
Communication Drivers would not add variable TimeStamps when tasks were executed in write.
|
8602
|
Design
|
When a project was transferred to a WinCE device with heavy files, the transfer would fail generating an error message in the trace.
|
8623
|
Design
|
The "Set Screen Alias" from the Command List would cause problems in objects with animated movements and/or set scaling.
|
8640
|
Networking
|
The network connection between Client and Server using the Parent and Child techniques would result very slow compared to using direct techniques.
|
8868
|
OPC Communication
|
When browsing OPC tags in a Server with many tags, it would take minutes to accomplish.
|
8702
|
OPC Communication
|
A signal regarding the OPC Manager would appear repeatedly in the "error.log" file.
|
8846
|
Real Time DB
|
The execution of a high number of basic script expression would cause slow page changes.
|
8679
|
Real Time DB
|
In the Grid object would freeze when User logged On using the PostgreSQL.
|
8544
|
Real Time DB
|
When a structure type variable being Traced changed its quality, one record was recorded for the structure plus one record for each of its individual members was recorded in the Trace as well. This has been fixed so that when the Trace is enabled for the variable structure as a whole, only one record will be recorded for the whole variable structure when the variable changes quality.
|
8673
|
Redudancy
|
The redundancy synchronization file would get created as ANSI type in UNICODE projects. This would then raise an error in Movicon during the synchronization phase.
|
8610
|
Screen Objects
|
The "InsertRow" method from the "GridWndCmdTarget" basic script interface would remain pending while being executed.
|
8687
|
Screen Objects
|
The "Acknowledge All" and "Reset All" would not work correctly when executed from a Client project's Alarm Window. These commands when executed from Client now execute the acknowledgement and reset of those alarms displayed in the Client Alarm Window.
|
8735
|
Screen Objects
|
The basic script Query property in the Grid object would raise and error.
|
8691
|
Screen Objects
|
The Grid object would remain in cell selection mode when the mouse was released outside the object.
|
8769
|
Setup
|
During uninstall phase the Movicon Setup would not delete all the files. The skeyinst.log and setupex.xco files would not delete.
|
8629
|
WebClient
|
A screen loaded by a Web Client would in certain cases remain pending without being destroyed.
|
8782
|
WebClient
|
In certain conditions the Web Client session would become unstable and consume the WebClient License.
|
7604
|
WebClient
|
In certain cases, when executing change pages frequently from Web Client, the web page would remain empty and the initial page had to be reloaded in order to continue.
|
8658
|
WinCE OS
|
In certain cases running a project in Windows CE 5.0, scroll bars from the List-Box and Combo-Box objects would go missing and would not show again.
|
8630
|
WinCE OS
|
When using a monocromatic Windows CE device, graphical problems would verify in some objects.
|