ID
|
TOPIC
|
PROBLEM FIXED
|
11821
|
Alarm Management
|
An alarm would remain ON when the variable would turn to OFF while the Alarm was still executing the threshold script.
|
11882
|
Alarm Management
|
The multilanguage text in the Alarm Window would not get handled correctly if it was in the variable's value place holder %(VariableName) description.
|
11460
|
Customization (Movicon BA)
|
Movicon BA showed the Movicon icon in the Windows bar.
|
11131
|
Data Loggers Management
|
The problem involving the Out of memory when using a great number of data loggers (around 300) which recorded according to set time intervals has been fixed.
|
11564
|
Design
|
Importing a database within the editor creator would not create the data logger, variable and columns correctly. In addition all the variables were created as string types if the database type was an SQL Server.
|
11776
|
Design
|
Movicon would freeze when importing a UDT which existed as a prototype in the RTDB.
|
11793
|
Design
|
The Enable and Disable methods or Dynamic OPC Groups would have not effect in the Implicit OPC Groups.
|
11456
|
Design
|
The Data Analysis would get printed with a black background.
|
11718
|
Design
|
The Edit Pen window would not show the "Data Logger Column" field when opened with the "Add" button.
|
11775
|
Design
|
Data Analysis - The First Point and Last Point buttons moved the cursor to the second and penultimate sample respectively.
|
11396
|
Documentation
|
Using the F1 key to open the Help online in a resource selected from the project was incorrect in the English language version.
|
7028
|
OPC Communication
|
When associating an OPC group to a variable in the log, the group's activation/deactivation message would not show.
|
10857
|
Real Time DB
|
Import Database: importing the structure of a DB as recipe type would create the variables incorrectly.
|
11023
|
Real Time DB
|
Trace - The AuditTrail comment would be requested even when variable had not been modified.
|
11702
|
Recipes Management
|
Recipe exportation would not work for columns that had Tags with integer structures.
|
12374
|
Redudancy
|
A primary project would generate an "Out Of Memory" error while synchronizing with the secondary project.
|
11367
|
Report Management
|
Dword values would not get read correctly from the database in Embedded Reports.
|
11572
|
Report Management
|
The Memory Leak in the embedded reports management on the Windows CE platform has been fixed.
|
11255
|
Screen Management
|
The "ScreenToLoad" system variable would ignore values that were higher than the SHORT range.
|
12351
|
Screen Management
|
An object which set its visibility according to the zoom level would be visible when it shouldn't have been.
|
11392
|
Screen Objects
|
The Xpos function of an object invoked from script for the first time would not execute properly.
|
12209
|
Screen Objects
|
Movicon would freeze when the alarms or log messages were scrolled using the mouse wheel in the Alarm Window or Historical Log.
|
11505
|
Screen Objects
|
The combo box could not find the linked variable if loaded in an embedded screen which displayed child screen.
|
11399
|
Screen Objects
|
Updating public symbols failed to work correctly when contained in an embedded screen.
|
11130
|
Screen Objects
|
The "template project" wizard would set the font node in trends and the historical log by error.
|
11575
|
Screen Objects
|
Trend : When the first configured pen would always be considered as being selected even though not visible in the legend.
|
11307
|
Screen Objects
|
The alarm window would order alarms based on the second column and not according to time on.
|
10699
|
Screen Objects
|
Request for the option to disable the display of labels on points of the DataAnalysis curve.
|
12120
|
Screen Objects
|
Display problems would occur using the "Analysis" button in a Trend Template taken from Symbol library.
|
11056
|
Screen Objects
|
Using vectorial images in buttons would cause delay in displaying the page.
|
11930
|
Setup
|
Starting up Movicon in DEMO from the Windows start menu would cause problems displaying reports.
|
11199
|
Setup
|
the setup would install WinCe components from 11.3.1104.
|
9480
|
Tools
|
The 'Invalid Argument' error during string importation has been fixed.
|
12452
|
User Interface
|
"BCGPOleAcc - Could not get the Class ID!" error has been fixed.
|
11719
|
WebClient
|
iOS: La password inserted in the settings was not encrypted.
|
11296
|
WebClient
|
The iOS App startup would not consider current screen orientation.
|
11592
|
WebClient
|
iOS: page loading progress and server connection interruption indications have been added.
|
11194
|
WebClient
|
The Apple iOS App performed a continuous image refresh when Screen quality was not set at 100 percent.
|
11295
|
WebClient
|
The Apple iOS App would startup with different resolutions to those set in the screen.
|
11195
|
WebClient
|
The Apple iOS App splash Screen would show a non-updated version number.
|
11201
|
WinCE OS
|
The Green and Red rectangular button management was incorrect in Windows CE.
|