ID
|
TOPIC
|
FIXED PROBLEMS
|
14671
|
Alarm Management
|
In some cases the milliseconds reported in the Time columns of the Alarm Window and the relating Temporary Historical were wrong.
|
16678
|
Alarm Management
|
The Alarm Banner would not update the current value of the variable inserted in the alarm text if the page, in which the Banner had been inserted, had not been reloaded.
|
16225
|
Basic Script
|
The GetTimeStamp() function from the DBVarObjCmdTarget interface would return the wrong data in cases when the system's minutes were comprised in the >0 and <6 range.
|
14268
|
Data Logger Management
|
In some cases the RestoreFlushedData would not restore data correctly. Note: the tool used the "ODBCTokenForSpaces" registry key to identify the start and end characters for the column name used by the specific Data Base Gesture when the names contained spaces.
|
15972
|
Data Loggers Management
|
Data Logger column names would duplicate when using the Copy and Paste from the Edit menu. This would not happen when using the CTRL+C and CTRL+V shortcuts.
|
16270
|
Design
|
The CTRL+SHIFT+S command for saving all the project's modified resources ('Save All') would not function.
|
16346
|
Design
|
The Contextual Help would not open in the DBVarObjCmdTarget's GetTimeStampMS() function.
|
16505
|
Design
|
When the Cross Reference List opened with a selected variable, even though the variable was still selected in RealtimeDB but without focus, it would get eliminated from the RealtimeDB when the Canc key was pressed.
|
15646
|
Design
|
The 'Create Recipe Screen' Wizard would not create the temporary variables with the correct names if the Recipe was set with Structure type variables.
|
14888
|
Design
|
When the Transparent Animation was linked to a Variable that changed value, the animation present in other objects would slow down when this happened.
|
15112
|
Design
|
The Grid object's "ColumnsWidth" property would not function correctly when the Grid was populated by VB Script.
|
16477
|
IL Logic
|
"Logica IL" editor would lose any modifications that were not confirmed before being closed.
|
15323
|
Menu Resources
|
The 'Help failed to open' error message would show when selecting the "Help Basic Script" item from the Help menu of a Basic Script Resource.
|
16565
|
Networking
|
The Audit trace on the Networking Client side would provide the Server with information about the logged in user who changed the variable on the Client side even when the 'Enable CFR21-PART11' property had been set to true on that Client.
|
16025
|
Networking
|
The Client would go into server connection timeout without resolving the error. Now the "Number of attempts to Connect" property from the "Advanced TCP Transport Settings" property group has been set to the 0 value (default 10) to allow the closing and reopening of a new connection socket to the Server's TCP/IP port after the number or retries has been reached in order to retrieve the Client project's connection Timeout error.
|
14661
|
Networking
|
The Alarm Window of the Client configured for a contemporary connection to a Primary and Secondary would not connect automatically to a Secondary Server when the Primary Server was nolonger available. In any case, even when the Secondary became unavailable the Client would not automatically retry to connect after a certain number attempts to do so in order to avoid causing an infinite loop of requests. This made it necessary to update manually (F5).
|
16591
|
Networking
|
The Movicon Windows (Such as the Alarm Window, Historical Log Window and the TraceDB window) that can be connected to a Networking Server would authenticate with the user used on the Client side for logging on to the Client application. Now, when the Servers use a "Default User" for authenticating the Networking clients, the Movicon client windows use the authentication towards the Server independently from the user logged on to the Client in a certain instant.
|
8364
|
Networking
|
Using the "Local Transport" would cause a delay in exchanging data between a Networking Client and Server project.
|
15153
|
ODBC
|
Activating the "ODBC Real Time I/O Link" option in a String type variable would cause ODBC errors such as 'incorrect syntax' in cases where the string variable contents were deleted and therefore resulted as being empty.
|
16576
|
OPC Communication
|
Movicon would raise an exception when closed after having execuing a failed search for an OPC Server UA.
|
15099
|
Real Time DB
|
When an alarm was set with an access mask other than the default value, a 'Resource Access Denied' message would show upon acknowledging or resetting the alarm if there no user had logged on.
|
15996
|
Redudancy
|
In cases where the Movicon "OPC Server" has been configured active in the Primary and Secondary project, the OPC Server in the Secondary project would disable when the Primary project was active. Now both the Priimary and Secondary OPC Servers are activated.
|
15674
|
Redudancy
|
The Startup Script would not execute when the Secondary Server reactivated in response to the unavailability of the Primary Server.
|
15858
|
Redundancy
|
In case where structure variable members were exchanged with the field directly (enabling the activation option of each individual member), the member quality would not update correctly on the Secondary Server o on the Client the Primary Server changed. In addition, when the "inherit Quality" property was set, those members not connected to the field would get set with the "Not Good" quality when a communication error occured in the structure variable but they would not get reset back to the "Good" quality when the error was resolved.
|
16074
|
Redundancy
|
The Startup Script would not execute on the Secondary Server if the Script resource "Run on Server" property had been purposely disabled and if the Primary Server was activated correctly.
|
14993
|
Redundancy
|
When the "Switch on (on Secondary) Driver error (of the Primary Driver)" property was active, the Secondary drivers would switch off instead of switching over from the Primary when the Primary was nolonger available in network.
|
14721
|
Screen Management
|
An error would occur in the Movicon .cpp modules when using Windows 8 and CoDeSys Driver versions prior to 11.4.1.4
|
15320
|
Screen Management
|
The status viewer if enabled in objects would still continue to indicate the do not return off communication error after the communication error had been fixed.
|
15100
|
Screen Management
|
In Windows 8.1 it was not possible to interact with a Screen opened in Popup modale mode from a Screen with its "Enable Multi-touch2 option enabled. However this problem would not occur when Popup screen was opend in Frame mode.
|
15990
|
Screen Management
|
The "Pinch & Zoom" management in Multitouch systems has been improved and is now more precise with smoother zooming in and out.
|
15102
|
Screen Managemet
|
A screen Button, that was set with the On/Off mechanics in Touchscreen systems based on Windows 8.1, once pressed would activate the off command in the variable when losing focus instead of remaining pressed.
|
16298
|
Screen Objects
|
Some Library Symbols would be redrawn incorrectly on screen when changes were made to their XML code using the XML code Editor.
|
15704
|
Screen Objects
|
The "Duty Manager" Template symbol would not handle the On call duty Group users' descriptions in alphabetical order in the Runtime Users file used for managing the send priorities of alarm notifications.
|
15197
|
Screen Objects
|
Tje 'Historical Log Window" had visualization problems setting a filter query in alarms using the 'Wuery' property from the "HisLogCmdTarget" interface.
|
16291
|
Screen Objects
|
Some symbols from the Symbol Library have been updated to signal their incompatibility with the WinCE environment by setting the AvCE attribute ="0" in the node of the symbol in question.
|
16160
|
Setup
|
The new IEC61850 Driver has been added to the list of avialable Drivers.
|
14456
|
Setup
|
The help file of the installed languages would not install correctly when installing Movicon in the development environment in Turkish together with another language.
|
16419
|
Tools
|
The Tag Importer-exporter Tools allowed the importing of Tags whose names contained characters that are considered invalid for creating variables in the RealtimeDB.
|
15932
|
Tools
|
The SMTP Plugin settings would get saved in a file with the same name of the Hark Disk volume in the Main Project files and not with the "smtp_direct.settings"name in the Project's DATA folder.
|
16017
|
Tools
|
The CEUploadServer tool launched on the WinCE Panel would go into error when cancelling the project folder from the WinCE device using the 'Delete Device Memory Card' button from the "Transfer Project to Device" utility.
|
15715
|
Tools
|
The Alarm Dispatcher would go into error when sending an email with a considerably long body text due to not handling the data from the alarm log correctly.
|
16026
|
User Interface
|
When Movicon.exe and MoviconRuntime.exe were started up from the Terminal Service as Clients, they would not startup or shut down immediately due to incorrect reading of the General "MaxAppInstances" key. Now when the"MaxAppInstancess" value is set to 0, there will be no limits to the number of Movicon instances that can be started up in the system. Incompatibility: the "MaxAppInstances" 0 value is incompatible with previous versions which interpret this value as no Movicon processes to be started up.
|
16128
|
WinCE OS
|
The links used for installing Movicon CE from the Windows Start Menu would not install the CABs correctly.
|