Problems fixed with the version: 11.5.1181

 

Build: 11.5.1181
Release Date: 24th May 2016

ID

TOPIC

FIXED PROBLEMS

17136

Screen Management

A small memory leak while changing pages would occur when starting up the project in runtime using MoviconRuntime.exe, Movicon.exe /R, or MoviconService.exe.

 

 

Minor Problems

ID

TOPIC

FIXED PROBLEMS

17333

Alarm Management

The GetSelectedAlarm() function would return an '0x8000fff' error when an element from the Alarm Historical log was selected in the Alarm Window while enabling the Alarm Historical log to display temporarily.

 

17334

Design

When confirming renamed RealtimeDB variables using the "Apply New Name" or "Apply Renamed Variables and Resources" functions, the OPC Tag property would set to the old name and not the new one.

 

17119

Design

The Drivers.xml file contained the wrong Driver names and therefore they were displayed in the project incorrectly.

 

17191

Design

The ALT + '-' combination keys would raise and exception in Movicon in both Development and Runtime modes.

 

17123

ODBC

The default SQLServer2014 ODBC plugin would create the "SQLServer2012.settings" file in the project.

 

17351

OPC Communication

When the OPC UA Server exposed variables with VARIANT (id 24) Data Types, they would not display on the OPC UA Client Browser because it was not possible to create Variant variable types in Movicon.  It is now possible to display Variant type tags depending on the type of element data derived from the VARIANT tag value.  As it is not guaranteed that the server will provide the value when browsing, the elements are indicated with a (?) at the end of their name in order to distinguish them from those that have compatible types with those of Movicon.ariant.

 

17317

OPC Communication

The 'GetOPCUAClient' method was not available in the PmeDocCmdTarget for accessing the OPCUAClientCmdTarget interface.

 

17265

OPC Communication

An OPC UA Server that exposed Structure type variables would get acquired by the Movicon OPC Client UA without a reference to the structure instance.  Now Structure variable are acquired indicating the name of the structure variable instance.

 

17286

OPC Communication

The moment that variables changed to the "Not in Use" status in Movicon CE, an "Error modifying monitored for item" would show in the OPC UA Click log by error.

 

17269

OPC Communication

Variable quality would not change to the "Not Good" status in the OPC UA Client when the OPC UA Server no longer became available.

 

16975

OPC Communication

When selecting an Array tag from the OPC UA Server using the 'Add New OPC UA Tag' command, a scalar variable of the array elements would get created in the Movicon project and not the Array variable type exposed by the OPC UA Server.   

 

16041

Real Time DB

In a project containing several communication drivers, the "Apply Renamed Tags and Resources" command used for a variable connected to the field would modify the I/O physical address properties of the other project tags.

 

17323

Real Time DB

Once expressions in a screen's objects were valued, the variables would always remain In-use even when changing screen.

 

15494

Real Time DB

Saving a project with a name containing a retentive Array type would cause the Array's retentive data to get lost.

 

16905

Redundancy

The Secondary and the Primary would continously synchronize with each other due to continuous Driver notifications for updating variable values.  This problem was most prominent when using the S7TCP  Driver was used.

15101

Screen Management

Problems would occur using Touchscreen systems based on Windows 8.1.  For instance, if a screen's Multi-Touch option had been enabled, problems would occur when interacting with Display object spins which would remain pressed; or if the Audit Trail's Comment Window had not been enabled, it became impossible to interact with it once opened from a Display object.

 

16810

Screen Management

When an Embedded Screen object was present on screen, it would take time displaying its contents if the screen's "Expression Waiting Time" property had been set with a value different from zero.

 

16979

Screen Object

In cases where an expression value error has occurred in runtime, eg. for an alias that had not been valued correctly, this would influence the calculation results of the other expressions.

 

17426

Setup

The Pro.Lean 11.5.1180 Setup would install files in the Movicon 11.4 folder.

17387

WinCE OS

The PocketPC platform for WinCE systems is no longer supported as from the 11.5.1181 version.