ID |
TOPIC |
PROBLEM
FIXED |
19375 |
{Alarm Management}} |
Filters set using the "AlarmWndCmdTarget"
interface in the Alarm Window and Banner Window would
not get applied in runtime.
|
19799 |
{Comm.Drivers} |
When importing 'Structure Protoype'
variables while using the Wizard to create a new project,
they would get added to the project resource tree directly
instead of in the Structure Prototype Resource.
|
18124 |
{DataLogger Management}} |
The Data Logger set to record
'on change' and with Columns to record the connected Variable's
TimeStamp would stop recording the Variable's value if
the TimeStamp changed only (this did not happen
in previous Movicon versions).
|
19370 |
{Design} |
If the 'Show Window Border' option
of the startup screen was disable, launching the application
with full screen, the border belonging to Movicion's home
page would still display when receiving focus. Movicon's
home page window border no longer shows when starting
up at full screen with the 'Show Window Border' disabled.
|
19624 |
{Design} |
Opening several pop-ups in sequence
in Modal mode, the "_SysVar_:ActiveScreen"
system variable would not update when the last pop-up
closed.
|
19566 |
{Design} |
In Arrest mode a 'No error message
available' window would show caused by using simulation
system variables in expressions of Child projects which
used variables from the the Parent project. This
errror message or the 'failed to load document' message
would show during the application startup phase due to
the use of '#uses' clauses in diverse VB Script
that started up simultaneously and shared the #uses with
the same resources. This last problem would also
happen during runtiime when activating the Command List
when running many scripts.
|
19270 |
{OPC Communicatin} |
A
considerable amount of memory was consumed when the 'Watchdog'
property from the OPC DA Client Resource was set with
a value different from zero. The Memory Leak worsened
when the Watchdog's time value was lessened.
|
19820 |
{OPC Communication} |
Setting a Password level different
from zero in the 'OPC Server Access Level' property from
the 'OPC UA Server' group property of the project's 'Real
Tiime DB' resourse would block access to users with Password
levels lower than the one set. To make this work
correctly, the password management in the Server (Movicon)
must be enabled.
|
19824 |
{OPC Communication} |
If the OPC Server Access Level'
from the 'OPC Server' group of the 'Real Time DB' resource
was set with a value different to zero, access to the
OPC UA Server would be given to non-existing project
users set in the 'User Name' and 'Password' properties.
|
20167 |
{OPC Communication} |
The 'TimeStamp' value sent by
the Movicon OPC DA Server to OPC DA Clients would greatly
offset the difference in time between the PC's local time
and the UTC: "LocalTime" + "Time
Zone" + "Legal Time".
|
19480 |
{OPC Communication} |
A runtime, se la proprietà "Gestione
Tag in Uso" del "Real Time DB" era impostata
a False, i Tag OPC UA Client del progetto non si collegavano
col Server OPC UA.
|
15558 |
{OPC Communication} |
The connection to a B&R's
OPC UA server would fail when using the OPC Server UA
browser window if the 'User Name and Password' authentication
was performed with the "Security Level" set
at 'None'.
|
19430 |
{OPC Communication} |
The Movicon OPC Client DA would
resend the 'True' Boolean value as '-1' in a Networkking
configuration (or Redundancy) if sent by the Movicon Server
and as '1' if sent by the Movicon Client. Now, both
the Movicon Server and Client projects send the '-1' value
as a 'True' Boolean value.
|
19487 |
{OPC Communication} |
Connecting to the Server UA Sample
Server, some Variant data types not supported by Movicon
11, would generate an exception when sending new data.
Now selecting Varian type tags is limited to those
containing array types supported by Movicon.
|
19668 |
{OPC Communication} |
Sudden variable value changes
in the OPC UA Client would cause the OPC UA Server to
assume the wrong values. This problem began following
the fact that notifications arriving from the OPC UA Server
were not syncronized with the variable input. text.
Two properties have been added to make the OPC Tag
Readable and/or Writable as required. For example,
if the variable is control with a timed impulse it must
be set in Write only to make it insensitive to latencies
of variation notifications arriving from the Server.
|
20084 |
{Report Management} |
The
"Signed DWord" data type was intepreted in the
report as an "Unsigned DWord" when the Data
Base type was a "SQL Server". This
could be fixed by using a work around to change the query
in a way so that the DWord field with sign would convert
to String eg: "Convert(VARCHAR,[ColumnName]) As 'ColumnName'.
|
19216 |
{Scheduler Resources |
The Scheduler resource set with
the Weekly planner with 00:00 to 23:59 hours for 7 days
a week, would not execute Off commands at the termination
of the last day and would not execute any other commands
for the following days without interacting with the Scheduler
Window. .
|
20039 |
{Screen Objects} |
When using the Preload Screens
property containing Trends or Data Analysis objects, the
Mouse pointer would blink alternating between the hour
glass and arrow image ata project startup.
|
16866 |
{Screen Objects} |
A sequence of particular operations
(inserting a new row and then selecting it) in the Movicon
Grid object would delete all the records from the table
when pressing the Grid's 'Delete' button.
|
18842 |
{Screen Objects} |
Pens set Retangle type in the
"Data Analysis" object would get designed overlapping
each other due to their sizes thus making the chart unreadable.
|
20161 |
{Screen Objects} |
When the period showed in the
Trend with "Nr. Minor X Ticks" and "Nr
of Major X Ticks" values set in the Trend object
to show a value, recorded by the connected Data Logger,
in correspondence with each tick, the same time instance
would get shown on the X axis during Runtime.
|
20073 |
{Screen Objects} |
A popup opened with a 'Keep Pressed'
command would re-open spontaneously after closing.
|
19293 |
{Screen Objects} |
The Horizontal 'D' type switch
had an inverted graphics animation in respect to the variable
value for which it showed the 'ON' image when the connected
variable vlaue = '0'.
|
19459 |
{User Interface |
Clicking on an object's scrollbar
to scroll it, if the mouse moved away from the scrollbar
the scrolling would stop. Now, scrolling only stops
when releasing the mouse key indifferently to where the
mouse is situated.
|
20083 |
{User Management} |
Setting the value = '1' in a user's
'Password Duration (Days)" parameter, the password
would expire 48 hours after the user was created instead
of 24 hours or the day after.
|
19398 |
{WinCE} |
When the project 'Gestures' option
had been enabled, when touching the Touch Screen, the
cursors coordinated did not match the position touched
by the finger. In addition, after closing a system
window, (eg. Numeric Pad or Login Window), the first click
on an object (eg. a button object) would not get intercepted
by that object without re-clicking it again.
|
19807 |
{WinCE OS} |
A screen containing a horizontal
Trend with connected pens connected to a project variable
instead of a Data Logger, would not open properly
by freezing it's graphical interface. (This problem
started when resolving case 17055).
|
19215 |
{WinCE OS} |
A considerable amount of memory
was consumed in the Windows CE systems when clicking an
Internal Report's 'Save Internal Report' command.
|
19860 |
{WinCE OS} |
Tapping the 'Click' event within
an object's VB Script context with the Gesture property
enabled and the Multi-Touch disabled, the event would
not get executed.
|
19763 |
{WinCE OS} |
Enabling the Multi-touch and using
the Touch panel in an object to activate an "OnRelease"
command, this command would activate even when releasing
the finger tip outside the control. This would
only happen in Windows CE using finger tips and not the
mouse.
|
18406 |
{WinCE OS} |
When a Display object had been
enbled, the Numeric Pad in Windows CE Multi-touch systems
would open when clicking outside the Display.
|
19206 |
{WinCE OS} |
If a cascade of Popups opened
in Frame mode when editing data using the Numeric Pad,
they would go in background in respect to the background
screen therefore hidden from view when closing the Pad.
Now they remain in the foreground in respect to
the background screen when closing the Pad.
|