ID |
TOPIC |
PROBLEM
FIXED |
17525 |
Design |
The Trend and Data Logger Symbol
Library would lose reference to the connected Date Logger
Resource. Now when you insert a new symbol on screen,
the relative Data Logger resource is created.
|
16565 |
Networking |
When Client networking, the Trace
Audit provides the Server with information on the logged
on User who changed the variable on the Client side (even
if server is a secondary server) providing that the 'Enable
CFR21-PART11' property on that Client has been set to
'true'.
|
8364 |
Networking |
Exchanging Data between Networking
Client and Server projects would take longer than usual
when using Local Transport.
|
16591 |
Networking |
The Movicon Windows (such as the
Alarm window, TraceDB window and Historical Log wnidow)
that can connect to a Networking Server would authenticate
with the user logged on to the Client application at that
moment. Now, when the Server uses a 'Default User'
for authenticating Networking Client users, the Movicon
Client windows uses that user for authenticating towards
the Server independently form the user logged on to the
Client at that moment.
|
22013 |
OPC Communication |
When setting the Access Rights
to 'Ready' only in the Project's Varialbe Options, an
external OPC UA Client could still modify the Movicon
Tag in Write.
|
22011 |
OPC Communication |
Some S7-1500 PLC data types would
not get detected correctly when browsing the OPC UA Server,
exposed by the PLC, with Movicon. Apparently, some
data types in these plcs are not coded as standard types
even though they match. Now, the data type is also determined
on the type of data transmitted as value. In addition,
the LWord and Lint data types are still unavailable as
they are 63 bit integers which do not match possible Movicon11
variables.
|
16578 |
Screen Management |
When opening a PopUp, the data
in the window underneath would not update. Apparently
the appearance of the Password Request window would interrupt
notifications to objects independently from the value
in the key [General\DynObjPumpIteration] which now
is exclusively used to slow down variation messages to
objects which is handy when the hardware used has scarse
resource. The key's default value is now '0'.
|
18740 |
Screen Object |
The Trend's or Data Analysis'
'DataFilterBy' function from a Client project (traditional
or Parent/Child but not from Web Client) would not execture
the query towards the Server correctly. The data retrieved
now are correct but in function with the Client Trend
or Data Analysis object's 'Execution - Max rows' property
value.
|
22452 |
Screen Objects |
A command associated to a rotated
Rectangle object would executed even when clicked outside
the object's area.
|
21254 |
Screen Objects |
The Toolbox's NumericPad symbol
would generate an incorrect tag.
|
21657 |
OPC Communication |
The OPC UA Client Certificate
is now automatically created when Browse the OPC UA Server
or at the first start of the Runtime if it does not exist. |